Features of production:

The amorphous core transformer above has its core made of an amorphous alloy that improves its electrical characteristics and significantly reduces energy loss. In comparison with the conventional transformer, its no-load loss drops by 75% on average.

Below are specifications of different sizes of this transformer:

U17-25/11

Capacity(kVA): 25
Vector group: Dyn11
No load loss (W): 26
Load loss (W): 207
Impedance voltage (%): 4

U17-50/11

Capacity(kVA): 50
Vector group: Dyn11
No load loss (W): 48
Load loss (W): 432
Impedance voltage (%): 4

U17-100/11

Capacity(kVA): 100
Vector group: Dyn11
No load loss (W): 84
Load loss (W): 700
Impedance voltage (%): 4

U17-200/11

Capacity(kVA): 200
Vector group: Dyn11
No load loss (W): 160
Load loss (W): 1228
Impedance voltage (%): 4

U17-315/11

Capacity(kVA): 315
Vector group: Dyn11
No load loss (W): 223
Load loss (W): 1927
Impedance voltage (%): 4

U17-500/11

Capacity(kVA): 500
Vector group: Dyn11
No load loss (W): 350
Load loss (W): 2370
Impedance voltage (%): 4